70000cmh Combined Sections AHU. ZK series combined air-conditioning unit is a new type of air treatment equipment developed by HEAD-POWER based on accumulated years of central air-conditioning production experience. It has beautiful appearance, compact structure, convenient installation and maintenance, good rigidity and air leakage rate. Low-level features; according to user requirements, a variety of functional segment combinations can be provided, which are widely used in industrial air-conditioning places such as electronic meters, precision machinery manufacturing, textiles, chemicals, cigarettes, pharmaceuticals, food, power stations, etc. Supermarkets, theaters, exhibition centers, gymnasiums, shopping malls, hotels, office buildings and other high-use and civil air-conditioned places for large and medium-sized public buildings
Send Inquiry
Chat Now

70000cmh Combined Sections AHU

The air-conditioning box itself will be equipped with a corresponding control system, and the start-up of the air-conditioning should follow the operation steps of the control system. In winter, the air conditioner is equipped with a humidification system such as spray, and in the case of winter use, it should be carried out according to a special startup sequence: first turn on the fan, then the burner, spray, surface cooling, heating, etc.;

Check and confirm the parameters of the air conditioning unit:

After the air conditioner is turned on, whether it is operating normally, or whether it can meet the process requirements, needs to be confirmed according to many parameters, including:

1. Air conditioner motor current: According to the rated power of the motor, the current of the motor during normal operation can be determined, and the actual motor operating current should be close to it;

2. The pressure difference of junior, middle-efficiency and high-efficiency filters: These pressure difference values can reflect the use of various filters, and the value can be read on the micro differential pressure meter installed on the air conditioner. At a specific wind speed, the filter normally has a constant differential pressure value. For example, the differential pressure value displayed on the differential pressure gauge is much higher than the differential pressure value (more than twice the initial resistance), indicating that the filter needs to be replaced or Cleaning (cleanable filter); Reference pressure difference of the filter: initial effect: ≦50Pa; intermediate effect: ≦80Pa; high efficiency: ≦100Pa;

3. Inlet and outlet pressure of chilled water in the surface cooler: The surface cooler generally requires the pressure of the chilled water to be 3 kg for the inlet water and 2 kg for the outlet water.

4. Temperature of inlet and outlet of chilled water of surface cooler: inlet temperature requires 7-9℃; outlet temperature will change due to different load. Generally at 10-15°C.

Regularly check the tension and wear of the fan belt. Press the belt by hand and feel tight; if it is obviously loose, it should be tightened in time; if the belt is seriously worn, it should be replaced in time;

*Note: The power supply should be cut off completely when entering the fan room, pay attention to safety!

When the surface cooler heater is deactivated, it is very important to drain the internal water (in winter) to prevent frost cracking.




4

9.FAQ


Cindy Li 名片



Hot Tags: 70000cmh combined sections ahu, China, manufacturers, customized, quotation, low price, made in China, Air Handling Unit Function For Laboratory, Horizontal Air Handling Unit, Clean Room Air Handling Units, 26kw Air Handling Unit, Clean Room Air Handling Units 100KW, 25000 M3 h Air Handling Unit