Cautions For Installation Of Water Chiller

Sep 25, 2019 Leave a message

The steam compression chiller consists of four main components of a vapor compression refrigeration cycle (compressor, evaporator, condenser, part metering device) that can implement different refrigerants. The following should be noted during installation:

1. Please check if the machine is damaged during installation. Choose the right place for installation and future maintenance.

2. The site where the unit is installed must be the floor, the installation mat or the foundation, its level is within 6.4mm, and can withstand the operating weight of the unit.

3. The unit should be placed in a machine room with a room temperature of 4.4-43.3 ° C. There should be sufficient space around and above the unit for routine maintenance.

4. At the end of the unit, leave a pipe space for cleaning the condenser tube bundle. You can also use a door hole or other suitable hole.

5. Select the water pipe of the appropriate pipe diameter? The cooling system and the cold water system of the maximum power operation of the unit are connected correctly.

6. For common applications, the water flow rate through the evaporator and condenser is allowed to be between 1.0 and 3.6 m/s.

7. Under any load conditions, the water flow should remain stable.

8. All chilled water and cooling water piping should be designed and installed in accordance with conventional methods. The chilled water pump should be located on the inlet pipe of the unit to ensure positive pressure and flow within the unit. The piping should be provided with a damping tube to ensure proper flexibility, and to prevent the evaporator water from being drained when the pump is shut down. The piping should have a solid support independent of the chiller to avoid stress being applied to the components of the chiller. The hangers are set up to facilitate pipe alignment.

9. In order to reduce noise and vibration, it is best to install a vibration isolator on the pipeline.

10. In order to use the chiller economically and efficiently, please ask the water treatment expert to analyze the water quality of the evaporator and condenser. The bad water quality will cause the fouling to affect the heat transfer, or cause corrosion and sedimentation, breeding organic matter, affecting the performance of the unit. Operating and maintenance costs. Bus processing machine

11. In general, correct water treatment and periodic cleaning of the bundle can maintain its good performance. If the existing water quality conditions cannot be improved by appropriate methods, then it is necessary to consider allowing the bundle to have a large fouling factor or designation. Special structural materials.

12. Please install a filter at the entrance of the water pipe and clean it regularly.

13. All the nozzles must be rust-proof after the test leak is completed.

To facilitate daily maintenance during installation, the user can use some (or all) of the following measures: A pressure gauge and shut-off valve with cock can be installed on the inlet and outlet pipes of cooling water and chilled water? Try to be close to the chiller; B Hanging rails and beams can be placed above the equipment for easy maintenance.